
Above is a curve comparing the overhead condenser heat transfer with
the RVP attainable. This curve illustrates how much the
overhead condenser fouling affects the bottoms RVP. The base
case operation reflecting the survey conditions is shown at
the lower left of the curve. The minimum simulation RVP
attainable is 7.3 with essentially no C4- in the
bottoms. The other data points on the same line indicate how
much the gasoline RVP increases as the overhead condenser heat
transfer coefficient is reduced. All of the points below the
dashed line denoting the survey U of 44 represent feasible
operating points. The top curve estimates the effect of higher
cooling water temperatures and hence RVP’s in the summer.
Almost all of the points are above the existing U dashed line
indicating that the operation is unfeasible with the fouled
exchangers. All of the runs maintained the same 1.7 LV%
C5+ in the overhead LPG.
The curve clearly shows how much the
survey heat transfer coefficient was below design. The curve
for the current winter operation indicates that the RVP could
be reduced only marginally by removing all of the
C4-. The curve for summer operation shows the large
impact that the poor heat transfer coefficient would have in
the coming months. Assuming that the exchanger heat transfer
coefficient remained constant, the fouled overhead condensers
would result in FCCU gasoline RVP’s above 12. This
unacceptably high RVP forced a resolution.
Return to RVP Equipment
Fouling